Distribution Board Components and Protection Groups

Status

This document defines the agreed target behavior for distribution-board components, protected circuit groups and circuit protection devices. Phase A and the relational Phase-B1 foundation are implemented; later sections remain requirements and are not proof of runtime or editor support.

Full rule-based protection and cable sizing is deliberately deferred. This phase establishes the structure and manually selected technical values that a later calculation and warning engine will evaluate.

Goals

  • represent the circuit list as the basis of a tabular single-line diagram
  • list incoming, group-level and auxiliary distribution-board components with stable equipment identifiers
  • support multiple independently protected groups for lighting, single-phase and three-phase outgoing circuits
  • give every newly created outgoing circuit one explicit protection device
  • preserve the existing distinction between a circuit and its device rows
  • keep every structural change atomic, revisioned and persistently undoable
  • prepare stable target fields for the later Revit round-trip

Non-Goals

  • norm-compliant protection or cable sizing
  • automatic creation of additional groups based on the incoming rating
  • automatic phase balancing
  • manufacturer-specific product catalogs
  • automatic equipment-identifier generation for auxiliary components
  • channel-level relationships between actors and controlled circuits
  • PostgreSQL or multi-user operation

Existing Model Audit

Keep

  • Circuit remains the outgoing-circuit aggregate.
  • CircuitDeviceRow remains a load assigned to a circuit and never receives its own protection device or equipment identifier.
  • Circuit-level load, cable and control fields remain circuit-owned.
  • Existing stable UUIDs, project revisions, snapshots and persistent Undo/Redo remain authoritative.
  • CircuitSection remains the migration starting point for a protected circuit group.
  • Grid projection remains separate from persisted domain structure.

Change

  • A CircuitSection gains an explicit category and group number and represents one protected circuit group.
  • Circuit protection changes from loosely related flat strings to an explicit one-to-one protection-device model.
  • Distribution-board components become independent BMK-bearing list entries.
  • Equipment-identifier uniqueness covers circuits and all distribution-board components in the complete circuit list.
  • Moving a circuit to another group of the same category atomically assigns the next identifier of the target group.
  • New distribution boards create three default groups rather than treating the optional unassigned compatibility section as a normal fourth group.

Remove Eventually

  • hard-coded assumptions that each category has exactly one section
  • numbering that only understands prefix + integer
  • free-text protection-device combinations that cannot be validated
  • rcdAssignment as a substitute for an explicit group relationship

Removal happens only after migrated state, snapshots, commands and the editor use the replacement model.

Target Domain Structure

Project
└── DistributionBoard
    └── CircuitList
        ├── fixed header components
        │   ├── Main switch
        │   └── Surge protective device
        ├── CircuitGroup 1..n
        │   ├── optional upstream protection component
        │   ├── optional group RCD component
        │   └── Circuit 0..n
        │       ├── ProtectionDevice exactly 1
        │       └── CircuitDeviceRow 0..n
        └── auxiliary components 0..n

The hierarchy defines ownership and electrical grouping. It does not require every level to be visually indented in the table.

Circuit Groups

CircuitSection evolves into the circuit-group entity. A group has:

  • stable UUID
  • circuit-list ownership
  • category
  • positive group number
  • display name
  • sort order
  • optional upstream protection component
  • optional group RCD component
  • zero or more outgoing circuits

Supported categories:

  • lighting
  • single_phase
  • three_phase

Each new distribution board creates exactly:

  1. Beleuchtung 1
  2. 1-phasig 1
  3. 3-phasig 1

Additional groups are created manually. A new group receives the highest existing group number in its category plus one. Gaps are not filled automatically.

A group may have at most one upstream protection component and at most one group RCD. Both are optional. Every circuit in the group remains downstream of those group components until it is moved to another group.

Distribution-Board Components

Every distribution-board component has:

  • stable UUID
  • circuit-list ownership
  • unique equipment identifier
  • name
  • role
  • placement
  • sort order within its placement

Initial roles:

  • main_switch
  • surge_protective_device
  • group_upstream_protection
  • group_residual_current_protection
  • auxiliary

Initial placement zones:

  • header
  • group
  • footer

New distribution boards create exactly:

  • -Q0, name Hauptschalter, role main_switch
  • -FA, name Überspannungsableiter, role surge_protective_device

These fixed components appear at the top and may initially have no further technical product data.

Auxiliary components initially require only:

  • manually entered equipment identifier
  • name
  • sort order

Examples include KNX switching actuators, blind actuators, phase-monitoring modules, DALI gateways, relays and other installed board equipment. They appear after all circuit groups and can be reordered by drag-and-drop. Automatic BMK suggestions and channel-to-circuit relationships are deferred.

Circuit Protection

Every newly created outgoing circuit owns exactly one protection device. CircuitDeviceRow does not own a protection device.

The circuit and its protection device are projected as one circuit row. The circuit equipment identifier is also the displayed identifier of its protection device and must not be stored twice.

Supported protection-device types:

  • D02
  • NH000
  • NH00
  • NH0
  • NH1
  • NH2
  • NH3
  • LS
  • FI
  • FI_LS
  • AFDD

D01 and NH4 are intentionally excluded.

Protection-Device Fields

All protection devices have:

  • type
  • rated current in ampere

Type-dependent fields:

  • D02 and NH:
    • fuse utilization category gG or gR
  • LS:
    • trip characteristic B, C, D or Z
  • FI:
    • RCD type A, AC, B or B+
    • rated residual current in milliampere
  • FI/LS:
    • trip characteristic B, C, D or Z
    • RCD type A, AC, B or B+
    • rated residual current in milliampere
  • AFDD:
    • trip characteristic B, C, D or Z
    • no RCD type
    • no rated residual current

Poles are intentionally not stored. The circuit-group category supplies the required phase context for the current scope.

Allowed Ratings

D02

20, 25, 32, 35, 40, 50, 63 A

NH000 and NH00

6, 10, 16, 20, 25, 32, 35, 40, 50, 63, 80, 100, 125, 160 A

NH0

6, 10, 16, 20, 25, 32, 35, 40, 50, 63, 80, 100, 125, 160, 200, 224, 250 A

NH1

16, 20, 25, 32, 35, 40, 50, 63, 80, 100, 125, 160, 200, 224, 250 A

NH2

25, 32, 35, 40, 50, 63, 80, 100, 125, 160, 200, 224, 250, 300, 315, 355, 400 A

NH3

50, 63, 80, 100, 125, 160, 200, 224, 250, 315, 355, 400, 500, 630, 800 A

LS, FI/LS and AFDD

6, 10, 13, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 A

FI/RCD

Rated currents:

16, 25, 40, 63, 80, 100, 125 A

Rated residual currents:

10, 30, 100, 300, 500 mA

The device type determines which values and characteristics are valid. UI, request validation and domain validation use one shared catalog rather than duplicated free-text rules.

All supported devices that provide overcurrent protection may be selected as a group upstream protection device. A standalone FI belongs in the separate optional group-RCD role.

Default Protection Devices

New circuits receive:

  • lighting:
    • LS
    • 10 A
    • characteristic B
  • single-phase:
    • FI/LS
    • 16 A
    • characteristic B
    • RCD type A
    • 30 mA
  • three-phase:
    • FI/LS
    • 16 A
    • characteristic B
    • RCD type A
    • 30 mA

A newly added group RCD defaults to:

  • FI
  • 40 A
  • RCD type A
  • 30 mA

An upstream protection component has no automatic default and is created only when the planner requests it.

Equipment-Identifier Rules

The leading hyphen is part of every generated identifier.

Group 1 examples:

-1F1.0  upstream protection, lighting
-1Q1.0  group RCD, lighting
-1F1.1  first lighting circuit

-2F1.0  upstream protection, single-phase
-2Q1.0  group RCD, single-phase
-2F1.1  first single-phase circuit

-3F1.0  upstream protection, three-phase
-3Q1.0  group RCD, three-phase
-3F1.1  first three-phase circuit

Category numbers:

  • lighting: 1
  • single-phase: 2
  • three-phase: 3

Function letters:

  • overcurrent protection and outgoing circuit: F
  • group RCD: Q

The group number follows the function letter. .0 is reserved for the group component. Outgoing-circuit suffixes start at .1.

Equipment identifiers must be unique across all circuits and components of the complete circuit list, including header and footer components.

Manual BMK edits must validate that same shared uniqueness boundary.

Reorder, Move and Renumber Behavior

Reorder Within One Group

Changing circuit order changes only sortOrder. It never changes an equipment identifier.

Move to Another Group

A circuit may move only to another group of the same category.

The move:

  1. finds the highest existing outgoing-circuit suffix in the target group
  2. assigns that suffix plus one
  3. moves the complete circuit, its one-to-one protection device and all device rows
  4. commits old and new group, position and identifier atomically

Gaps are not filled. Undo restores the original group, sort position and equipment identifier. Redo reapplies the same previously determined target identifier rather than calculating another one.

This automatic identifier change is specific to a cross-group move initiated by the user. A reorder inside one group never renumbers.

Reorder Groups

Changing group display order changes only group sortOrder. Group numbers and all equipment identifiers remain unchanged.

Explicitly Renumber Groups

Group renumbering is a separate explicit action. It:

  • changes group numbers according to the requested mapping
  • preserves every outgoing circuit suffix
  • updates optional .0 group-component identifiers
  • updates every affected circuit identifier
  • resolves swaps through collision-safe temporary identifiers
  • commits the complete mapping as one project revision

Undo restores the exact previous group numbers and identifiers.

Delete Behavior

A group may be deleted even when populated, but only after an explicit warning that summarizes:

  • optional upstream protection
  • optional group RCD
  • number of circuits
  • number of circuit device rows

Confirmation deletes the complete group subtree atomically. The inverse command stores the complete stable snapshots needed to restore all UUIDs, fields, links, protection devices, group relationships, identifiers and sort positions.

A stale or partially changed subtree must not be silently deleted or restored.

UI Projection

The circuit-list editor projects three fixed zones:

  1. header:
    • -Q0 Hauptschalter
    • -FA Überspannungsableiter
  2. groups:
    • group heading
    • optional upstream protection row
    • optional group RCD row
    • circuit rows and their optional expanded device rows
  3. footer:
    • auxiliary distribution-board components

Group indentation is optional presentation. Group ownership must remain clear through headings, separators or a dedicated group indication.

The grid remains a custom spreadsheet component:

  • static text by default
  • edit mode only when invoked
  • group and auxiliary-component drag handles
  • clear valid and invalid drop indicators
  • German user-facing labels

Protection editing must show only fields valid for the selected device type. Changing the type resets or explicitly confirms removal of fields that the new type cannot use.

History and Command Boundary

New project-scoped writes must use typed persistent commands and the existing shared project-command transaction boundary.

Required logical operations:

  • insert/update/delete auxiliary component
  • reorder auxiliary components
  • insert/update/delete group protection component
  • insert/delete group
  • reorder groups
  • explicitly renumber groups
  • move circuit between same-category groups with deterministic BMK assignment
  • update circuit protection device

Creating a distribution board includes its fixed components, three default groups, circuit list and all stable UUIDs in one distribution-board.insert command.

Every command must:

  • require expectedRevision
  • validate complete project/list/group ownership
  • validate shared BMK uniqueness inside the write transaction
  • contain deterministic forward and inverse data
  • commit the domain mutation, revision and history transition atomically
  • remain undoable and redoable after application restart

Snapshot and Transfer Compatibility

The supported logical project snapshot and portable JSON transfer must include:

  • group category and group number
  • fixed, group and auxiliary components
  • circuit protection-device state
  • all new component relationships and sort positions

Introducing the model requires a snapshot-schema version increase and explicit upgraders for supported older payloads.

Database migration rules:

  • preserve all existing stable UUIDs
  • preserve existing circuit equipment identifiers during schema migration
  • map the existing lighting, single-phase and three-phase sections to group 1 of the respective category
  • preserve an existing unassigned section only when required by existing data; it is not created for a new distribution board
  • preserve existing flat circuit protection values when creating the new one-to-one protection state
  • do not silently replace an existing protection selection with a new default
  • allow legacy identifiers to remain until an explicit, collision-safe conversion or renumber action is approved

New defaults apply to newly created circuits and boards, not as an implicit rewrite of existing planning data.

Historical persisted commands and snapshots that remain in the supported compatibility window must still deserialize and execute after the migration.

Later Sizing and Warning Engine

The selected protection device is the planner-owned value. Later sizing logic will calculate a recommendation separately.

Target behavior:

stored selection
    -> calculation and validation
        -> valid: no warning
        -> invalid: colored warning plus recommended protection
            -> user explicitly accepts or rejects the recommendation

The same pattern applies later to cable cross-section and length. Suggestions never silently overwrite selected values.

Dimensioning rules and additional inputs are defined in a separate future specification supplied by the planner.

Delivery Phases

A. Catalog and Pure Domain Rules

Status: Complete.

  • introduce typed component roles, categories and protection-device types
  • centralize rating and characteristic catalogs
  • validate device-specific field combinations
  • define default circuit and group-RCD protection values
  • test numbering parsing and formatting independently from persistence

Implemented foundation:

  • shared circuit-group categories, German labels and category numbers
  • one protection-device catalog with all agreed ratings and characteristics
  • strict device-dependent validation for fuse, LS, FI, FI/LS and AFDD fields
  • pure factories for circuit and group-RCD defaults
  • pure nested BMK formatting, parsing and highest-number-plus-one rules
  • no runtime database or editor integration before delivery phase B

Acceptance:

  • every agreed valid combination is accepted
  • invalid rating/type/field combinations are rejected
  • defaults produce the exact agreed values

B. Persistence and Compatibility Model

Status: Complete.

  • add group category and group number
  • add distribution-board component persistence
  • add one-to-one circuit protection persistence
  • implement shared BMK uniqueness
  • generate and inspect one additive migration
  • add snapshot/transfer schema upgrade
  • preserve existing identifiers and protection values

Implemented in B1:

  • additive migration 0024 adds group identity to circuit sections and maps the three established sections to group 1 without changing UUIDs
  • separate component and circuit/component protection tables preserve the one-to-one ownership boundaries
  • a trigger-maintained circuit-list registry rejects normalized BMK collisions across circuits and distribution-board components
  • the existing flat circuit protection fields remain untouched until their deterministic snapshot/runtime transition is implemented
  • clean and populated pre-migration databases are covered by migration tests
  • newly created legacy-compatible board structures receive the same initial group identity while their persisted command format remains unchanged

Implemented in B2:

  • snapshot schema version 7 includes group identity, distribution-board components and both one-to-one protection collections
  • capture, named and automatic snapshots, restore, Undo/Redo and portable JSON transfers preserve the complete new relational state
  • duplicate imports remap component UUIDs and both protection-owner references together with the existing project structure
  • versions 1 through 6 remain readable; version 6 maps the three established section keys to group 1 and leaves new collections empty
  • older flat circuit protection values remain present and are not guessed into strict new protection configurations
  • current snapshots reject invalid ownership, duplicate group numbers, cross-entity BMKs and invalid protection configurations before persistence

Acceptance:

  • a current database migrates without data loss
  • an empty database creates the complete schema
  • old supported snapshots and transfers upgrade deterministically
  • BMK collisions across circuits and components are rejected

C. Persistent Commands and Board Defaults

Status: In progress. New-board defaults C1 are complete; component and group management commands C2 are pending.

  • extend distribution-board.insert with fixed components and three groups
  • implement component and group CRUD commands
  • implement group and footer reordering
  • add complete inverse snapshots and rollback tests

Implemented in C1:

  • distribution-board.insert schema version 3 carries stable UUIDs for three initial groups, main switch -Q0 and surge protective device -FA
  • its inverse verifies and removes the unchanged complete structure; Redo restores the same UUIDs
  • a late revision/history failure rolls back board, list, groups and components together
  • stored schema versions 1 and 2 retain four legacy sections and receive no invented components

Acceptance:

  • new boards contain the agreed fixed structure
  • every structural write survives reload and supports Undo/Redo
  • forced late failures leave no partial components or groups

D. Group Numbering and Circuit Moves

  • implement nested identifier generation
  • support same-category cross-group circuit moves
  • implement explicit collision-safe group renumbering
  • implement confirmed populated-group deletion

Acceptance:

  • target identifiers use highest suffix plus one
  • reordering never renumbers
  • cross-category moves are rejected
  • group renumbering preserves circuit suffixes
  • delete, move and renumber Undo restore exact prior UUIDs and BMKs

E. Editor Projection and Editing

  • render fixed header components
  • render group components and circuit blocks
  • render sortable auxiliary footer components
  • add group management and destructive confirmations
  • add type-dependent protection editing
  • keep spreadsheet selection, keyboard and drag behavior coherent

Acceptance:

  • the visible order is header, groups, footer
  • users can create, configure, reorder and delete groups
  • users can configure circuit and group protection without invalid fields
  • device rows remain visually and technically subordinate to their circuit

F. Documentation and Full Verification

  • update current architecture, API and interaction documentation
  • update demo/sample data
  • run focused domain and transaction tests
  • run the complete required test, build and type-check suite
  • perform the agreed GUI test checklist

Acceptance:

  • documentation distinguishes implemented behavior from later sizing
  • clean install and migrated database both work
  • snapshots, JSON transfer and Undo/Redo cover all new state

Risks and Mitigations

  • Mixed legacy and grouped BMKs: preserve old identifiers and provide an explicit conversion path.
  • Cross-entity BMK collisions: enforce one transaction-level uniqueness boundary for the complete list.
  • Partial destructive writes: persist complete subtree commands through the shared transaction wrapper.
  • Bloated grid logic: add pure projection and ownership modules before React rendering changes.
  • Invalid protection combinations: use one shared typed catalog for UI, API and domain validation.
  • Silent planning changes: apply defaults only on creation and keep later recommendations explicit.
  • Snapshot incompatibility: version payloads and test every supported upgrade path.

Open Implementation Decisions

These decisions may be resolved during the relevant delivery phase without changing the agreed domain behavior:

  • exact relational implementation of the shared BMK ownership boundary
  • presentation of group ownership through indentation, headings or a column
  • filter behavior for structural component rows
  • explicit UI for converting retained legacy identifiers to grouped numbering
  • whether fixed header components become editable beyond name and BMK in this phase